  gamewell-fci 12 clintonville road, northford, ct 06472-1610 usa ? tel: (203) 484-7161 ? fax: (203) 484-7118 specifications are for information only, are not intended for installation purposes, a nd are subject to change without notice. no responsibility is assumed by gamewell-fci for their use. ?2013 by honeywell international inc. all rights reserved. www.gamewell-fci.com 9020-0542 rev. j page 1 of 4 incc and e3 loc, incc cab-b intelligent network command center s1869 city of chicago approved city of denver approved 7165-1703:0125 class 1 class 2 high rise signaling approved 3025415 fm fdny coa # 6077 mea approved description the gamewell-fci, incc in telligent network command center serves as the point of interface between an opera- tor and the system?s audio evac uation, fire fighter inter- com, and building control circuits. it is a component of the following systems. ?e3 series ? expandable emergency evacuation ? e3 series combined fire and mass notification system ? e3 series broadband audio evacuation system ?netsolo ? system the incc occupies a single node along the e3 broadband network and is connected by a single pair of twisted, unshielded wire, fiber-optic cable or any combination of the two. each e3 broadband node can be spaced along the network at a maximum distance of 3,000 feet (914.4 m) or up to an 8db loss using fiber-optic cable. built-in isola- tion at each node permits style 4, style 6, and style 7 net- work configurations. the e3 series broadband audio evacuation system is a peer-to-peer, self-regenerating, token ring network com- prised of up to 64 individual nodes. in addition, the addressable node expander (anx) board expands the network to 122 nodes. the e3 broadband employs proven technology and extends it to accomplish emergency voice evacuation, 2-way fire fighter communications, and build- ing control applications. it is unique in the industry because it requires only a single pair of wires or a fiber- optic cable connection between nodes to convey all fire alarm, digital voice, fire fighter communications, paging, and building control signals. the typical incc and e3 loc, incc-cab-b sub-assem- blies consist of the following: ? an intelligent network interface-voice gateway (ini-vgc) module ? one or more addressable switch modules (asm-16) ? one network graphic touchscreen annunciator (nga) the incc command center?s ini-vgc module also pro- vides connections for an optional emergency voice page microphone as well as a fire fighter telephone handset. the ini-vgc is a fully digita l voice/tone generator using state-of-the-art digital signal processing (dsp) technol- ogy to produce the clearest, most audible signal possible. the ini-vgc provides an output to a local speaker for message verification and testing. it is ideal for a wide range of complex system applications including high-rise or campus installations. features ? listed under ul ? standard 864, 9th edition. ? listed under ul standard ul2572 for mass notificatio n. ? all communication signals and control-by-event sequences over twisted, unshielded pair of wires or fiber-optic cable including: - audio evacuation - fan control & damper shutdown - voice paging - door closures - fire fighter intercom - fire alarm and control devices - elevator control - horn/strove circuit activation ? distributed architecture, including style 7 wiring config- urations, allow system components to continue normal operation with no loss of function during single line fault conditions. ? integrates with inx transponders and additional incc command centers to create a complete audio evacua- tion system with up to 122 nodes. ? each ini-vgc supports up to 16 asm-16 switch mod- ules for a total of 256 switches. ? ini-vgc connects to a voice page microphone and fire fighter?s handset. ? redundant command centers with microphone and fire fighter?s handset can be easily configured by adding additional inccs. ? advance boolean logic-based programming such as and, or, not, nor, time delay, and calendar func- tions configurable through computer programming. ? advanced digital signal processor (dsp) technology for efficient audio compression and filtering. uses network data transfer rate at 625k baud. incc
gamewell-fci 12 clintonville road, northford, ct 06472-1610 us a ? tel: (203) 484-7161 ? fax: (203) 484-7118 9020-0542 rev. j page 2 of 4 www.gamewell-fci.com figure 1 incc with mic and handset figure 2 incc with 6 asm-16s description (continued) each addressable switch module (asm-16) has 16 push- button switches that can be programmed to serve any function the application demands. an asm-16 switch can be programmed as any of the following: ? speaker circuit switch ? fire fighter phone switch ? auxiliary control switch using a bank of 3 switches (1 switch can be used for each on-off-auto function) ? switches with the following custom-defined functions? - system reset - all-call - system silence - phone patch - system acknowledge - lamp test - alarm tone on - manual select each asm-16 switch also has 3 fully programmable sta- tus-indicating leds in red, yellow, and green. the nga lcd graphic annunciator is a powerful, yet attractive com- ponent of the gamewell-fci emergency voice evacuation system. the bright, back-lit 1/4? vga display is supple- mented with an intuitive, ea sy-to-use touch-screen inter- face that provides the following features: ? up to 512 user-defined messages may be configured. ? messages may be up to 77 characters in length. ? display font and color may be selected for each message. the incc assembly is enclosed in one or more compact 19? wall-mounted enclosures. its modular construction provides complete flexibility in system design. each cabi- net can contain the ini-vgc and up to six asm-16 mod- ules. if more asm-16 modules are required, they may be mounted in additional incc cabinets. as many as six asm-16 modules can fit in th e incc cabinet. if a micro- phone module is required, it would take the place of 1 asm-16 position. a fire fighter handset would take the place of 2 asm-16 positions. an ini-vgc can support as many as 16 asm-16s for a to tal of 256 completely pro- grammable switches. the incc operates on 24 vd c that can be sourced from the non-resettable auxiliary output of its associated power supply such as the pm-9 or pm-9g. a complete e3 series audio evacuation system can be assembled from the following 3 different panels. this mod- ular approach greatly simplifies the design and installation process and can be configured to meet the exact needs of the project. ? one or more e3 series fire alarm control panels. ? one or more incc audio evacuation command centers. ? one or more inx transponders. ? one acu (autonomous control unit). ? one loc (remote local operating console). e3 series ? and netsolo ? are registered trademarks of honeywell international inc. ul ? is a registered trademark of underwriters laboratories inc.
gamewell-fci 12 clintonville road, northford, ct 06472-1610 usa ? tel: (203) 484-7161 ? fax: (203) 484-7118 www.gamewell-fci.com 9020-0542 rev. j page 3 of 4 figure 3 incc and e3 loc, incc-cab-b assemblies incc inner door shown with asm-16 handset & microphone inner door assembly incc backbox with ini-vgc
gamewell-fci 12 clintonville road, northford, ct 06472-1610 us a ? tel: (203) 484-7161 ? fax: (203) 484-7118 9020-0542 rev. j page 4 of 4 www.gamewell-fci.com specifications ini-vgc operating voltage: 24 vdc (nominal) operating current: 0.150 amp. supervisory and alarm operating temperature: 32 to 120 f (0 to 49 c) relative humidity: 0 to 93% (non-condensing) protocol asynchronous with half-duplex data flow speed rs-232 up to 64 kbps rs-485 up to 128 kbps st connectors up to 200 microns (multi-mode), optimized for 62.5/125 microns. asm-16 operating voltage: 24 vdc (nominal) operating current: 0.005 amp supervisory 0.005 amp alarm plus 0.003 amp per led activated (0.195 amp max.) operating temperature: 32 to 120 f (0 to 49 c) relative humidity: 0 to 93% (non-condensing) ordering information part number description intelligent network command center ini-vgc command center voice gateway. asm-16 programmable switch module (occupies 1 single slot on the inner door). incc-mic paging microphone module. incc-tel fire fighter telephone module. incc-idt inner door with 1 double slot (used for the incc-tel fire fighter handset) and 4 single slots. incc-id inner door with 6 single slots. incc-cab incc backbox (black) with black outer door. dimensions: 19? w x 19? h x 4? d (48 w x 48 h x 10 d cm) incc-cabr incc backbox (black) with red outer door dimensions: 19? w x 19? h x 4? d (48 w x 48 h x 10 d cm)


▲Up To Search▲   

 
Price & Availability of INI-VGC-13

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X